Division 28 - Fire Graphics Map
- This information provides guidelines for Fire Graphics Maps.
- Graphics Map Details
- Building Plans: Scaled floor plans must be permanently mounted adjacent to the annunciator panels. These plans should cover every building level, including Mezzanines, Attics, Roofs, and Hidden Spaces.
- Essential Information:
- Name and address of the building or business.
- North arrow for orientation.
- Fire alarm symbol legend to understand different icons.
- Date of map installation.
- "You are here" symbol indicating the viewer's current location.
- Clearly legible room names and numbers.
- Location of the Fire Alarm Panel.
- Location of the Annunciator Panel.
- Location of the Sprinkler Valve Riser Room.
- Location of the Mechanical Rooms.
- Location of the Electrical Rooms.
- Location of Sprinkler Riser Valves.
- Location and zone numbers of Areas of Evacuation Assistance.
- Location of Chemical Fire Suppression.
- Zone Identification:
- Segregation lines, hash marks, or shading to clearly delineate fire alarm zones.
- Fire alarm system notification zones should align with building smoke and fire zones (not required for addressable FACPs).
- Device Indications (for point-lit graphic annunciators): Discrete LED indications for each alarm and supervisory initiating device.
- Graphics Map Specifications
- Construction: The map should be durable, easily readable in normal lighting, and protected by a smooth, transparent plastic surface. 1/8” inch anti-glare acrylic pane.
- Size: Minimum Size 18" x 24" or larger if required to accurately represent the facility.
- Frame Color: Black or Silver, Red stripe optional however not required
- Paper Type and Print:
- Indoor Conditioned Space – Bond
- Outdoor Protected Unconditioned Space – Vinyl or Approved moisture resistant equivalent. White with black lines and lettering.
- Updates: Maps should be updated to reflect current building layouts after any construction or modifications that change the building layout or device placement.
- Graphics Map Location
- General Location: Located within 10 feet of the Fire Annunciator Panel.
- Graphics Map Mounting: Brackets shall be concealed using a hidden “T Screw” type system for security.