Division 26 - Electrical Switchgear-Primary Metering

  1. This section provides minimum guidelines for the procurement and installation of primary metering on building loads served through main distribution switchgear panels. The basis for this standard is the Electro Industries/Gauge Tech Shark® 250, Bacnet/IP Communicating Multifunction Power Meter. Equivalent or better power metering technology appropriate for this application is acceptable.
  2. Required features/capabilities:
    • Multifunction measurements of AC voltage, current, power, and energy.
    • Utilize advanced DSP technology, high sampling rates, and 24 bit analog to digital conversion.
    • 0.2% or better energy class accuracy with compliance to modern ANSI and IEC accuracy standards.
    • Revenue grade power meter with native BACnet / IP 100BaseT Ethernet Protocol Utility grade test pulse allowing verification of performance to rated accuracy.
    • A Modbus TCP socket that can be used to simultaneously poll through the device.
    • Availability in meter or transducer version.
    • Integrate seamlessly into campus BACS. 
    • Industrial rated design.
    • Required to be BACNET Testing Laboratory (BTL) Certified.
  3. Additional preferred features:
    • Utility block and rolling average demand.
    • Adjustable demand profiles.
    • Voltage provides instantaneous maximum and minimum for surge and sag limits.
    • Optical IrDA port, allowing the unit to be set up and programmed using a remote laptop PC without the need for a communication cable.
  4. Isolation:
    • All inputs and outputs are galvanically isolated to 2500 Volts AC.
  5. Meter accuracy
    Measured Parameters Accuracy % of Reading Display Range
    Voltage L-N 0.1% 0-9999 V or kV Scalable
    Voltage L-L  0.1% 0-9999 V or kV Scalable
    Current 0.1% 0-9999 Amps or kAmps
    +/- Watts 0.2% 0-9999 Watts, kWatts, MWatts
    +/- Wh 0.2% 5 to 8 Digits Programmable
    +/- VARs 1.0% 0-9999 VARs, KVARs, MVARs
    +/- VARh 1.0% 5 to 8 Digits Programmable
    VA 1.0% 0-9999 VA, kVA, MVA
    VAh 1.0% 5 to 8 Digits Programmable
    PF 0.2% +/- 0.2 to 1.0
    Frequency +/- 0.01 Hz 45 to 65 Hz
    %THD  5.0% 0 to 100%
    % Load Bar  1-120% 10 Digit Resolution Scalable
  6. Compliance
    • IEC 62053-22 (Class 0.2S)
    • ANSI C12.20 (0.2% Accuracy Class)
    • ANSI (IEEE) C37.90.1 Surge Withstand
    • ANSI C62.41 (Burst)
    • EN 61000-6-2 – Immunity for Industrial Environments: 2005
    • EN 61000-6-4 – Emission Standards for Industrial Environments: 2007
    • EN 61326-1 – EMC Requirements: 2006
    • Certified to UL 61010-1 and CSA C22.2 No. 61010-1, UL File: E250818
    • REACH Compliant
    • RoHS Compliant
  7. Current transformers must meet IEC 57.13 – 0.3 B0.1 Accuracy (Solid Core) or Equal for New Construction.
  8. Current transformers must meet IEC 57.13 - 1.0 B0.1 Accuracy (Split Core) or Equal for Retro Fit Applications. ---------- With WWU Approval Only--------
     